Wall ties, often called brick ties, are the metal or polymer fixings built into the mortar joints of brick veneer to tie the brick skin to the frame behind it. In the NCC 2022 Housing Provisions they are covered by clause 5.6.5, which requires ties complying with AS 2699.1, sets light or medium duty by wind class, gives spacing and placement tables, and sets corrosion protection by distance from breaking surf or salt water. Clause 5.6.5 is a Deemed-to-Satisfy provision with conditions in Volume Two clause H1D5. This note quotes NCC 2022. The ABCB records that NCC 2025 was published on 1 May 2026, and lists South Australia as “BCA: 1 May 2027” and “PCA: 1 May 2026”. Which edition applies to a particular application is for the relevant authority assessing the building work to confirm.

What do wall ties do in a brick veneer house?
In masonry veneer, the brick leaf stands outside a timber or steel frame and is tied to it. Volume Two clause H1D5(1)(c) lists, among the conditions for using Part 5.2 of the Housing Provisions, that “the framing that the masonry wall is tied to complies with H1D6”.
Clause 5.6.5 begins: “Masonry wall ties must— comply with AS 2699.1”, then sets the duty, spacing, placement and corrosion protection. The notes to Table 5.6.5c state: “Ties to be embedded a minimum of 50 mm into each masonry leaf” and “Masonry wall ties must be installed in such a manner as to prevent moisture travelling along the tie to the inner leaf of masonry or the frame.”
The same clause covers cavity masonry (double brick), where ties join two masonry leaves. For engaged piers installed to support subfloor framing, NCC 2022 clause 5.2.6(f) states that the piers must be tied or bonded to the external masonry wall and that any ties used must comply with 5.6.5.
Which duty of wall tie does the NCC call for?
Clause 5.6.5(a) states that for masonry veneer walls ties must be “a minimum of light duty veneer ties in areas where the design wind speed is not more than N2” and “a minimum of medium duty veneer ties in areas where the design wind speed is more than N2”.
For cavity masonry walls the threshold is lower: “a minimum of light duty cavity ties in areas where the design wind speed is N1” and “a minimum of medium duty cavity ties in areas where the design wind speed is more than N1”. The clause adds that “where non-engaged piers are provided, piers must be tied to walls using medium duty ties” and that monolithic or solid masonry construction uses “a minimum of medium duty ties”.
The notes to Tables 5.6.5a and 5.6.5b state: “Wall ties that are suitable for higher duties are also suitable for use in lower duty conditions.” The wind rating note explains the NCC wind classes and how a site’s wind class is determined.
What is the wall tie spacing in brick veneer?
Clause 5.6.5(b) requires ties to “be spaced and fixed in accordance with Tables 5.6.5a, 5.6.5b and 5.6.5c”. Table 5.6.5a, “Wall tie spacings in masonry veneer”, ties the spacing to the stud spacing of the frame:
With 450 mm wall stud spacing: horizontal “Maximum 450 mm”, vertical “Maximum 600 mm”. With 600 mm wall stud spacing: horizontal “Maximum 600 mm”, vertical “Maximum 400 mm”.
Table 5.6.5b sets cavity masonry at a maximum of 600 mm horizontally and 600 mm vertically, and solid or monolithic masonry at 400 mm both ways. The Figure Notes add: “Where wall ties are required, they must be placed in adjacent courses (as shown) or must be placed in the same course on each side of the stud.”
Where do extra wall ties go around openings and edges?
Table 5.6.5c, “Placement of wall ties”, lists: unsupported panel sides and edges of openings, “Within 300 mm of panel side or edge”; top of veneer panels and top of panels under openings, “Within 300 mm or two courses (whichever is the lesser) of the top of veneer”; and the bottom of a veneer panel in a masonry rebate sealed with liquid applied damp-proof course, or supported on a steel lintel, “Within 300 mm or two courses (whichever is the lesser) from the bottom of the veneer”.
Where the bottom of the panel sits in a masonry rebate with a membrane damp-proof course, ties go “In each of the first two courses”. At the intersection of internal and external walls the table gives “350 mm vertically or 3-4 courses”, and at engaged piers “Within 200 mm of the top of the pier”.
Where articulation joints occur, ties go “At both sides of the articulation joint within 300 mm from the joint”. The articulation joints themselves are covered in a separate note.
How are brick ties protected against corrosion?
Clause 5.6.5(c) requires ties to “be protected against corrosion in accordance with Table 5.6.5d”, which sets three exposure conditions.
For “Areas less than 1km from breaking surf; or less than 100 m from salt water not subject to breaking surf; or within heavy industrial areas”, the minimum is “Grade 316L stainless steel; or engineered polymer complying with the requirements of AS 2699.1.”
For “Areas 1km or more but less than 10km from breaking surf; or 100m or more but less than 1km from salt water not subject to breaking surf”, the minimum is “Sheet steel and bar ties galvanised after manufacture - 470 g/m2 on each side; or galvanised wire ties - 470 g/m2 coating mass; or Grade 304L stainless steel.”
For “All other areas”, the minimum is “Galvanised sheet steel - 300 g/m2 coating on each side; or sheet steel ties galvanised after manufacture - 300 g/m2 on each side.” The explanatory information states that “stainless steel and engineered polymer ties are suitable for use in all conditions and 470g/m2 galvanised ties can be used in all exposure conditions except the most severe.” Steel lintels have a separate corrosion table, Table 5.6.7b, based on durability classes in AS 2699.3.
What about corroded wall ties in an existing house?
Clause 5.6.5 sets the ties to be used when masonry is built. The Housing Provisions text read for this note does not deal with inspecting or replacing ties in an existing wall.
Questions about ties in an existing wall are outside the clauses quoted here and are a matter for a structural engineer to advise on. Whether any repair work needs approval is for the council or relevant authority to confirm for the address.
Does clause 5.6.5 apply to all brick veneer construction in South Australia?
Clause 5.6.1(1) states that Part 5.6 “is subject to the limitations set out in H1D5(6)(c)(i), (ii) and (iii)”, and 5.6.1(2) states that it “need not be complied with if H1D5(6)(a) or (b) are complied with”. Volume Two clause H1D5(6) lists three routes for masonry accessories: AS 3700; AS 4773.1 and AS 4773.2; or Part 5.6 provided the building is in an area with a wind class of not more than N3, is not in an alpine area, and is one “for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.”
For masonry veneer, H1D5(1)(c) adds conditions to the Part 5.2 route, including a site soil classification of “A, S or M in accordance with AS 2870”. H1D5(1)(a) and (b) list AS 3700, and AS 4773.1 and AS 4773.2, as the other Deemed-to-Satisfy routes, and clause A2G1(2) allows a Performance Solution, a Deemed-to-Satisfy Solution, or a combination of the two.
The South Australian schedule to Volume Two varies Part H1 only by deleting H1P2 (buildings in flood areas); it contains no variation to H1D5. SA H2D4 deals with weatherproofing of masonry and does not mention wall ties. The South Australian schedule to the Housing Provisions lists Parts 4.2, 9.2, 10.2 and 13.1, not Part 5.6.
Who confirms the wall tie specification for a new house?
The tie type, duty, corrosion protection and spacing are recorded in the drawings and specification, and depend on the site’s wind class, exposure condition and the route chosen for the masonry. Whether the brickwork meets clause 5.6.5, the AS 3700 or AS 4773 route, or a Performance Solution is for the relevant authority assessing the building work to confirm.
Cavity flashings and weepholes, which sit in the same brick courses, are covered in a separate note.
Common Questions
What is the wall tie spacing for brick veneer?
Table 5.6.5a of the NCC 2022 Housing Provisions sets wall tie spacing in masonry veneer by the frame’s stud spacing: with 450 mm stud spacing, a maximum of 450 mm horizontally and 600 mm vertically; with 600 mm stud spacing, a maximum of 600 mm horizontally and 400 mm vertically. Table 5.6.5c adds ties near panel edges, openings, the top and bottom of veneer panels, wall intersections and articulation joints. Clause 5.6.5 is a Deemed-to-Satisfy provision subject to the conditions in Volume Two clause H1D5.
Do brick veneer walls need light duty or medium duty wall ties?
Clause 5.6.5(a) of the NCC 2022 Housing Provisions requires masonry veneer ties complying with AS 2699.1 to be “a minimum of light duty veneer ties in areas where the design wind speed is not more than N2” and “a minimum of medium duty veneer ties in areas where the design wind speed is more than N2”. The table notes state that ties suitable for higher duties are also suitable for lower duty conditions. Clause 5.6.5 is a Deemed-to-Satisfy provision, subject to the conditions in Volume Two clause H1D5.
What corrosion protection do wall ties need near the coast?
Table 5.6.5d of the NCC 2022 Housing Provisions requires Grade 316L stainless steel or engineered polymer complying with AS 2699.1 for areas less than 1 km from breaking surf, less than 100 m from salt water not subject to breaking surf, or within heavy industrial areas. From 1 km to less than 10 km from breaking surf, or 100 m to less than 1 km from other salt water, the table lists sheet steel and bar ties galvanised after manufacture at 470 g/m2 on each side, galvanised wire ties with a 470 g/m2 coating mass, or Grade 304L stainless steel. For all other areas, Table 5.6.5d lists galvanised sheet steel with a 300 g/m2 coating on each side, or sheet steel ties galvanised after manufacture at 300 g/m2 on each side; the explanatory information states that ties suitable for a more severe exposure condition are also suitable for less severe conditions. Clause 5.6.5 is a Deemed-to-Satisfy provision, subject to the conditions in Volume Two clause H1D5.
How far must brick ties be embedded in the mortar?
The notes to Table 5.6.5c of the NCC 2022 Housing Provisions state: “Ties to be embedded a minimum of 50 mm into each masonry leaf”, and that ties “must be installed in such a manner as to prevent moisture travelling along the tie to the inner leaf of masonry or the frame.” Clause 5.6.5 is a Deemed-to-Satisfy provision, subject to the conditions in Volume Two clause H1D5.
Does South Australia vary the NCC wall tie rules?
No South Australian variation to clause 5.6.5 of the NCC 2022 Housing Provisions was found: the Housing Provisions schedule for South Australia lists Parts 4.2, 9.2, 10.2 and 13.1, and the Volume Two schedule varies Part H1 only by deleting H1P2 (buildings in flood areas). NCC 2022 clause H1D5(6) lists AS 3700, AS 4773.1 together with AS 4773.2, or Part 5.6 as Deemed-to-Satisfy routes for masonry accessories; the Part 5.6 route is conditional on a wind class not exceeding N3, construction outside an alpine area, and no specific earthquake design requirements for the building under Appendix A of AS 1170.4.
Sources
- NCC 2022, ABCB Housing Provisions — Part 5.6 Masonry components and accessories (5.6.1, 5.6.5, Tables 5.6.5a–d, 5.6.7)Accessed 2026-11-23
- NCC 2022, ABCB Housing Provisions — Part 5.2 Masonry veneer (5.2.1, 5.2.6)Accessed 2026-11-23
- NCC 2022, ABCB Housing Provisions — Part 5.1 Scope and application of Section 5Accessed 2026-11-23
- NCC 2022 Volume Two — Part H1 Structure (H1D5)Accessed 2026-11-23
- NCC 2022 Volume Two — Part A2 Compliance with the NCC (A2G1)Accessed 2026-11-23
- NCC 2022 Volume Two — Schedule 8 South Australia, Part H1 Structure (SA H1P2)Accessed 2026-11-23
- NCC 2022 Volume Two — Schedule 8 South Australia, Part H2 Damp and weatherproofing (SA H2D4)Accessed 2026-11-23
- NCC 2022, ABCB Housing Provisions — Schedule 8 South Australia (index of variations)Accessed 2026-11-23
- ABCB — NCC 2025 state and territory adoption informationAccessed 2026-11-23
This page describes these sources as they stood on the access dates above. It is not legal advice about any particular property.